SIMULASI RELAI DIFFERENSIAL TERHADAP GANGGUAN INTERNAL DAN EKSTERNAL PADA TRANSFORMATOR 60 MVA APP UNGARAN MENGGUNAKAN SOFTWARE ETAP 12.6.0
Berkas Tugas Akhir
COVER.pdf
Restricted to Registered users only
ABSTRAK.pdf
Restricted to Registered users only
DAFTAR ISI.pdf
Restricted to Registered users only
DAFTAR PUSTAKA.pdf
Restricted to Registered users only
PUBLIKASI.pdf
Restricted to Registered users only
BAB 2.pdf
Restricted to Registered users only
BAB 1.pdf
Restricted to Registered users only
BAB 3.pdf
Restricted to Registered users only
BAB 4.pdf
Restricted to Registered users only
BAB 5.pdf
Restricted to Registered users only
Abstract
Sistem proteksi pada gardu induk sangatlah penting guna menghindari kerusakan peralatan listrik yang ada danjuga agar stabilitas penyaluran tenaga listrik tetap terjaga. Perlu adanya simulasi gangguan internal dan gangguan ekternal terhadap sistem proteksi pada transformator untuk mengetahui kehandalan sistem proteksi pada GI 150 KV Ungaran.
Setting relay differensial yang seseuai dengan standar PLN mempunyai nilai sebesar 0,3 A atau 30 % dengan alasan kesalahan CT 10%, mismatching 4%, kesalahan sadapan 10%, faktor keamanan 5% dan arus eksitasi 1%.Relay differensial akan bekerja apabila adanya gangguan internal saja. Dengan delay time sebesar 50 ms pada sisi 150 KV dan 83.3 pada sisi 20 KV.
Polaritas yang terbalik pada transformator arus 20 KV akan memberi inputan yang salah pada relay differential ketika terjadi gangguan ekternal. Hal ini dapat diatasidengan cara membalik polaritas pada transformator arus pada sisi tegangan rendah 20 KV.
Kata Kunci: Relay Differensial, Setting Relay, Gangguan